Features
Functions:
-4 or 8 digital inputs for switch sensors type as following :
mechanical switch contact
contact type PNP or NPN at solid state
inductive switch type NAMUR SJ2-N-Y
-Alarm status indication by 4 or 8 red LED integrated in the front panel
-Acknowledge pushbutton on front panel
-Test pushbutton on front panel
-Input configuration (N.O. or N.C) by pushbutton on front panel
-Auxiliary output for external cumulative alarm or additional external hooter programmable by pushbutton on front panel
Technical Specs
REGISTER
Register to view technical data and to download data sheets.
(EN)
Functions:
- Local and remote monitoring of tank for level and pressure
- Integrating differential and relative pressure transducers
- Large LCD display for level and pressure with backlight and low light sensor
- Minimum level, low pressure and high pressure/high level set-points with additional output switches programmable by user
- Low temperature alarm for detecting leakages of cryogenic media close the transducer.
- 3 additional alarm inputs for external switch sensors (e.g. pressure switches)
- Repeater signals 4/20mA or 0/20mA outputs for level and pressure measures
- Proprietary network protocol CRIONET or Modbus optional
- Programming by encoder with button integrated
- Easy, fast and inexpensive installation for setup and startup.
Power supply |
|
Voltage: |
24 Vdc ±5 % |
Current: |
max 0.2 A / 230 Vac |
Optional: |
max 100mA |
Additional alarm inputs: |
3 digital inputs, 9-48 Vdc, Imax 5 mA, insulation >4 kV |
Visual indications: |
4 digits LCD display for level H18 mm |
Pressure and level (DRT transducer) |
Relative pressure: |
Range: 0…20 bar (standard) |
Optional: |
0…50 bar (optional) |
Resolution: |
0.1 bar |
Combined error (0…50 °C): |
< ±0,2 bar |
Breaking overpressure: |
35 bar (80 bar for range 0…50 bar) |
Differential pressure (level) |
Range: |
0-2 bar |
Resolution: |
(programmable by user) |
Combined error (0…50°C): |
< ±2 % of F.S @ F.S. A150 mbar |
Differential overpressure: |
± 4 bar limited by integrated protection system |
Local network interface & References |
Local network interface: |
Proprietary protocol CRIONet on insulated RS485 |
Weight: |
3,5 kg |
Operating Temperature: |
-20…60 °C |
Reference standards and directives: |
014/30/EU EMC, 2014/35/EU LVD
EN 61000-6-1, EN 61000-6-3
ISO 15001, BAM M 034-1
|