AMBRA SISTEMI



We'd like to hear your message!

Contact us

SEND MESSAGE

DIGICONTROL

 

Features

 Functions:


-4 or 8 digital inputs for switch sensors type as following :
mechanical switch contact
contact type PNP or NPN at solid state
inductive switch type NAMUR SJ2-N-Y
-Alarm status indication by 4 or 8 red LED integrated in the front panel
-Acknowledge pushbutton on front panel
-Test pushbutton on front panel
-Input configuration (N.O. or N.C) by pushbutton on front panel
-Auxiliary output for external cumulative alarm or additional external hooter   programmable by pushbutton on front panel
 

Technical Specs

REGISTER

Register to view technical data and to download data sheets.

(EN)

Functions:

- Local and remote monitoring of tank for level and pressure
- Integrating differential and relative pressure transducers
- Large LCD display for level and pressure with backlight and low light sensor
- Minimum level, low pressure and high pressure/high level set-points with additional output switches programmable by user
- Low temperature alarm for detecting leakages of cryogenic media close the transducer.
- 3 additional alarm inputs for external switch sensors (e.g. pressure switches)
- Repeater signals 4/20mA or 0/20mA outputs for level and pressure measures
- Proprietary network protocol CRIONET or Modbus optional
- Programming by encoder with button integrated
- Easy, fast and inexpensive installation for setup and startup.

Power supply  
Voltage: 24 Vdc ±5 %
Current: max 0.2 A / 230 Vac
Optional: max 100mA
Additional alarm inputs: 3 digital inputs, 9-48 Vdc, Imax 5 mA, insulation >4 kV
Visual indications: 4 digits LCD display for level H18 mm
Pressure and level (DRT transducer)
Relative pressure: Range: 0…20 bar (standard)
Optional: 0…50 bar (optional)
Resolution: 0.1 bar
Combined error (0…50 °C): < ±0,2 bar
Breaking overpressure: 35 bar (80 bar for range 0…50 bar)
Differential pressure (level)
Range: 0-2 bar
Resolution: (programmable by user)
Combined error (0…50°C): < ±2 % of F.S @ F.S. A150 mbar
Differential overpressure: ± 4 bar limited by integrated protection system
Local network interface & References
Local network interface: Proprietary protocol CRIONet on insulated RS485
Weight: 3,5 kg
Operating Temperature: -20…60 °C
Reference standards and directives: 014/30/EU EMC, 2014/35/EU LVD
EN 61000-6-1, EN 61000-6-3